Features
- Corrosion Resistant Brass Construction
- 1-1/2” swivel inlet X 1-1/2”male outlet
- Eductor rated for optimum flow at 200 PSI (14 Bar)
- Furnished with 30”(76cm) pick up tube
- Variable metering valve
- Removable metering valve
- A large, easy to read metering dial
- Ball check valve prevents back flow into foam concentrate
Operating Procedures
- Must be used with a nozzle of equivalent flow rate
- Maximum hose lay between eductor and nozzle on level ground using 1½"(3.8 cm) hose is 150 ft.(46m)
- Maximum hose lay between eductor and nozzle on level ground using 2"(5 cm) hose is 300 ft.(91m)
- Normal inlet operating pressure at eductor is 200 psi; however, the eductor can be used at lower inlet pressures with a corresponding reduction in flow rates
* Pressure loss through the Chemguard eductor is approximately 35% of the inlet pressure
Suitable
- Suitable for use with water, AFFF, AR-AFFF, Fluoroprotein and Class “A” foam concentrates
Part No: | Description(lpm) | Material | Inlet | Weight(kg) | Proportioning Metering Valve |
|---|
CE60 | 60 GPM(227) | Brass | 1.5” NST | 10 LBS.(4.5) | .5%,1%,3%,6% |
CE60NPSH | 60 GPM(227) | Brass | 1.5” NPSH | 10 LBS.(4.5) | .5%,1%,3%,6% |
Part No: | Description |
|---|
CE95T | Pick Up Tube |
MV60 | Metering Valve for 60 GPM(227 lpm) Eductor |
MV95 | Metering Valve for 95 GPM(360 lpm) Eductor |
PTE | Pick Up Hose and Tube w/Clamps |